Home > NRC Library > ADAMS Public Documents
Forwards LERs 83-003/03L-0 & 83-004/03L-0.
Accession Number: ML20071D566
Date Released: Wednesday, March 25, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20071D563 - Forwards LERs 83-003/03L-0 & 83-004/03L-0. (1 page(s), 2/25/1983)
- ML20071D600 - LER 83-003/03L-0:on 830202,w/unit at 100% power & emergency diesel generator 3 out of svc for maint,containment vacuum pump,2-CV-P-1A,failed to develop flow.Caused by binding of sliding vanes in pump rotor.Pump replaced w/shop spare. (3 page(s), 2/25/1983)
- ML20071D640 - LER 83-004/03L-0:on 830204,w/unit at 100% power,amp reading for panel 9,circuit 20C below Tech Spec limits,due to failure of heat tracing circuit.Caused by open thermostat. Thermostat replaced & heat tracing circuit returned to svc. (2 page(s), 2/25/1983)