- ML20070K545 - Forwards LERs 82-047/03L-0,82-048/03L-0,82-049/03L-0 & 82-050/03L-0. (1 page(s), 12/23/1982)
- ML20070K580 - LER 82-047/03L-0:on 821124,during surveillance test review, air temp monitoring not performed within required time interval.Caused by personnel error.Requirement (FNP-2-STP- 63.0) revised to include performance of air temp monitoring. (1 page(s), 12/23/1982)
- ML20070K598 - LER 82-048/03L-0:on 821127,source range channel N-32 declared inoperable due to loss of detector voltage.Caused by faulty high voltage connector.Connector replaced. (1 page(s), 12/23/1982)
- ML20070K607 - LER 82-049/03L-0:on 821201,containment atmosphere activity monitors R-11 (particulate monitor) & R-12 (gaseous monitor) declared inoperable when vacuum pump tripped due to erroneous high flow signal.Caused by faulty high flow relay. (1 page(s), 12/23/1982)
- ML20070K619 - LER 82-050/03L-0:on 821124,source range channel N32 declared inoperable due to erratic readings.Caused by faulty detector on N31 & faulty high voltage power supply cable connector on N32.Detector & cable connector replaced. (1 page(s), 12/23/1982)