Home > NRC Library > ADAMS Public Documents
Forwards LERs 82-058/03L-0,82-044/03L-0 & 82-045/03L-0.
Accession Number: ML20066K295
Date Released: Friday, March 20, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20066K291 - Forwards LERs 82-058/03L-0,82-044/03L-0 & 82-045/03L-0. (1 page(s), 11/22/1982)
- ML20066K326 - LER 82-058/03L-0:on 821025,during performance of power range neutron flux channel calibr,overtemp-delta temp instrumentation loop declared inoperable.Caused by dirty contacts on printed circuit card C3-125.Contacts cleaned. (1 page(s), 11/22/1982)
- ML20066K363 - LER 82-044/03L-0:on 821023,during routine shutdown,turbine driven auxiliary feedwater pump declared inoperable when pump tripped.Caused by overspeed trip linkage being in tripped position.Trip linkage reset & returned to svc. (1 page(s), 11/22/1982)
- ML20066K392 - LER 82-045/03L-0:on 821023,during performance of pressurizer safety relief valve test,valves declared inoperable due to relief setpoint being out of tolerance.Caused by instrument setpoint drift.Setpoint adjusted & valves declared operable. (1 page(s), 11/22/1982)