Home > NRC Library > ADAMS Public Documents
Forwards updated LER 82-086/03X-1 & LERs 82-089/03L-0 & 82-090/03L-0.
Accession Number: ML20066A389
Date Released: Friday, March 20, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20066A387 - Forwards updated LER 82-086/03X-1 & LERs 82-089/03L-0 & 82-090/03L-0. (1 page(s), 10/27/1982)
- ML20066A395 - Updated LER 82-086/03X-1:on 820914,supply breaker for heat trace circuits tripped.Caused by loose aluminum wire connection at mechanical lug.Leads remade. (1 page(s), 10/27/1982)
- ML20066A408 - LER 82-089/03L-0:on 821005,during routine testing,roll up fire door 345 at transformer switchgear room did not close. No mechanical problems discovered.No further action planned. (1 page(s), 10/26/1982)
- ML20066A422 - LER 82-090/03L-0:on 821012,during routine surveillance,high vibration discovered at south safety injection pump.Cause not stated.Shaft straightened,impellers balanced,spacer sleeve,locknut & impeller hubs lapped & motor realigned. (1 page(s), 10/27/1982)