Home > NRC Library > ADAMS Public Documents
Forwards LERs 82-104/03L-0,82-105/04L-0 & 82-106/03L-0.
Accession Number: ML20064G489
Date Released: Wednesday, March 18, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20064G486 - Forwards LERs 82-104/03L-0,82-105/04L-0 & 82-106/03L-0. (1 page(s), 1/3/1983)
- ML20064G496 - LER 82-104/03L-0:on 821206,relay timer associated w/4 kV bus degraded voltage exceeded allowable value of 2 minutes & 6 s by 3.1 s.Caused by instrument drift.Timer adjusted. (1 page(s), 1/3/1983)
- ML20064G506 - LER 82-105/04L-0:on 821204,following sludge on steam generator 21,sludge lance lines found connected to east blowdown demineralizer,releasing unmonitored 200 gallons. Procedures misunderstood.Procedures will be revised. (1 page(s), 1/3/1983)
- ML20064G516 - LER 82-106/03L-0:on 821204,during surveillance test,4 kV circuit breaker 2C4 found to have inoperable anti-pump circuit.Caused by 250-volt dc control device malfunction,due to open circuit in anti-pump coil. (1 page(s), 1/3/1983)