Forwards LERs 82-044/03L-0,82-049/03L-0,82-050/03L-0, 82-051/03L-0,82-053/03L-0,82-057/03L-0,82-068/03L-0 & 82-071/03L-0.Detailed event analysis submitted.
Accession Number: ML20062M718
Date Released: Monday, March 16, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20062M716 - Forwards LERs 82-044/03L-0,82-049/03L-0,82-050/03L-0, 82-051/03L-0,82-053/03L-0,82-057/03L-0,82-068/03L-0 & 82-071/03L-0.Detailed event analysis submitted. (2 page(s), 8/13/1982)
- ML20062M773 - LER 82-044/03L-0:on 820715,condensate storage tank T-121 water level fell below Tech Spec limit on four occasions. Caused by inadequate makeup water control to tank.Tech Spec change initiated to install automatic level control. (1 page(s), 8/13/1982)
- ML20062M809 - LER 82-049/03L-0:on 820716,condensate storage tank T-121 water level fell below Tech Spec limit on two occasions. Caused by inadequate makeup water control to tank.Tech Spec change initiated to install automatic level control. (1 page(s), 8/13/1982)
- ML20062M834 - LER 82-050/03L-0:on 820717,condensate storage tank T-121 water level fell below Tech Spec limit on one occasion. Caused by inadequate makeup water control to tank.Tech Spec change initiated to install automatic level control. (1 page(s), 8/13/1982)
- ML20062M866 - LER 82-051/03L-0:on 820718,condensate storage tank T-121 water level fell below Tech Spec limit on three occasions. Caused by inadequate makeup water control to tank.Tech Spec change initiated to install automatic level control. (1 page(s), 8/13/1982)
- ML20062M889 - LER 82-053/03L-0:on 820719,condensate storage tank T-121 water level fell below Tech Spec limit on seven occasions. Caused by inadequate makeup water control to tank.Tech Spec change initiated to install automatic level control. (1 page(s), 8/13/1982)
- ML20062M931 - LER 82-057/03L-0:on 820720,condensate storage tank T-121 water level fell below Tech Spec limit on four occasions. Caused by inadequate makeup water control to tank.Tech Spec change initiated to install automatic level control. (1 page(s), 8/13/1982)
- ML20062M960 - LER 82-068/03L-0:on 820728,condensate storage tank T-121 water level fell below Tech Spec limit on two occasions. Caused by inadequate makeup water control to tank.Tech Spec change initiated to install automatic level control. (1 page(s), 8/13/1982)
- ML20062M982 - LER 82-071/03L-0:on 820727,condensate storage tank T-121 water level fell below Tech Spec limit on one occasion. Caused by inadequate makeup water control to tank.Tech Spec change initiated to install automatic level control. (1 page(s), 8/13/1982)