Home > NRC Library > ADAMS Public Documents
Forwards LERs 82-019/03L-0,82-023/03L-0,82-024/03L-0 & 82-020/03L-0.
Accession Number: ML20054E390
Date Released: Sunday, March 8, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20054E389 - Forwards LERs 82-019/03L-0,82-023/03L-0,82-024/03L-0 & 82-020/03L-0. (1 page(s), 6/2/1982)
- ML20054E393 - LER 82-019/03L-0:on 820508,exhaust fan failed to start, rendering B train penetration room filtration sys inoperable.Caused by worn fan belts which slipped off pulleys.Belts replaced. (1 page(s), 6/2/1982)
- ML20054E398 - LER 82-023/03L-0:on 820507 & 08,A train chlorine detector declared inoperable when tape drive failed & erroneous indication received,respectively.Caused by faulty gear drive motor assembly & improper loading of detector tape. (2 page(s), 6/2/1982)
- ML20054E402 - LER 82-024/03L-0:on 820510,A penetration room filtration sys declared inoperable when recirculation damper PRF-HV-3361B determined inoperable.Caused by control circuit power fuse blowing while electricians checked valve limit switches. (1 page(s), 6/2/1982)
- ML20054E407 - LER 82-020/03L-0:on 820504,snubber 2MS-R-530 declared inoperable since reservoir devoid of fluid.Caused by fluid leak on improperly installed O rings.O rings replaced & snubber declared operable. (1 page(s), 6/2/1982)