Home > NRC Library > ADAMS Public Documents
Forwards LERs 82-009/01T-0,82-010/01T-0 & 82-011/01T-0. Detailed event analysis submitted.
Accession Number: ML20053E974
Date Released: Friday, October 25, 2024
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20053E973 - Forwards LERs 82-009/01T-0,82-010/01T-0 & 82-011/01T-0. Detailed event analysis submitted. (4 page(s), 6/2/1982)
- ML20053E978 - LER 82-009/01T-0:on 820520,while performing type C leak tests on retention tank pump discharge valve,leakage flow rate found exceeding Tech Spec limit.Cause not stated. Valve relapped & restroked. (1 page(s), 6/2/1982)
- ML20053E983 - LER 82-010/01T-0:on 820521,while performing type C leak tests on containment bldg heating steam condensate return isolation valve,leakage flow rate found exceeding Tech Spec limit.Cause not stated.Valve internals replaced. (1 page(s), 6/2/1982)
- ML20053E985 - LER 82-011/01T-0:on 820523,while performing leak tests on high pressure svc water containment isolation valve & electrical penetration Unit 5,leak flow rate found exceeding Tech Spec limit.Caused by hardening of epoxy sealant. (2 page(s), 6/2/1982)