Home > NRC Library > ADAMS Public Documents
Forwards LERs 82-012/03L-0,82-014/03L-0 & 82-015/03L-0.
Accession Number: ML20052C134
Date Released: Friday, March 6, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20052C133 - Forwards LERs 82-012/03L-0,82-014/03L-0 & 82-015/03L-0. (1 page(s), 4/22/1982)
- ML20052C135 - LER 82-012/03L-0:on 820326,during routine insp,turbine driven auxiliary feedwater pump declared inoperable when outboard bearing oil bubbler found broken & oil drained. Possibly caused by workers handling scaffolding in area. (1 page(s), 4/22/1982)
- ML20052C137 - LER 82-014/03L-0:on 820328,while performing calibr & functional test,T average-low-low B instrumentation loop declared inoperable due to indicator reading.Caused by setpoint drift.Power supply card replaced. (1 page(s), 4/22/1982)
- ML20052C139 - LER 82-014/03L-0:on 820326,28 & 0408,B train chlorine detector declared inoperable due to detector tape not advancing.Caused by movement indicator binding detector tape & sheared pin in tape drive mechanism. (2 page(s), 4/22/1982)
- ML20052C140 - LER 82-015/03L-0:on 820325,radiation monitor R29B instrumentation channel declared inoperable when displays on all readout consoles were inaccurate.Caused by dirty contacts & faulty link.Contacts cleaned. (1 page(s), 4/22/1982)