Home > NRC Library > ADAMS Public Documents
Forwards LERs 82-007/03L-0,82-009/03L-0 & 82-010/03L-0.
Accession Number: ML20041B788
Date Released: Monday, February 24, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20041B787 - Forwards LERs 82-007/03L-0,82-009/03L-0 & 82-010/03L-0. (1 page(s), 2/18/1982)
- ML20041B794 - LER 82-007/03L-0:on 820122,during surveillance test,valve 2-CMO-429,component cooling water discharge from W RHR HX, failed to close.Caused by binding of valve shaft in stuffing box bore below packing due to buildup of corrosion. (1 page(s), 2/18/1982)
- ML20041B801 - LER 82-009/03L-0:on 820122,during normal operation,mounting bracket for turbine stop valve D,train A proximity switch discovered broken.Caused by excessive vibration.Bracket repaired & switch remounted. (1 page(s), 2/18/1982)
- ML20041B808 - LER 82-010/03L-0:on 820122,during surveillance test,valve 2-CO-420,W component cooling water HX discharge would not close remotely.Caused by binding of valve shaft in stuffing box bore below packing & in area of upper shaft bushing. (2 page(s), 2/18/1982)