Home > NRC Library > ADAMS Public Documents
Forwards LERs 82-004/03L-0,82-005/03L-0,82-006/03L-0 & 82-002/03L-0.
Accession Number: ML20041A426
Date Released: Monday, February 24, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20041A425 - Forwards LERs 82-004/03L-0,82-005/03L-0,82-006/03L-0 & 82-002/03L-0. (1 page(s), 2/8/1982)
- ML20041A431 - LER 82-004/03L-0:on 820112,fire hydrants 1-FP-89,1-FP-63, 1-FP-73 & 1-FP-98 would not open.Caused by freezing of stagnant water in body of hydrant due to unusually low temp. Frequency of insps to be increased during winter months. (2 page(s), 2/8/1982)
- ML20041A435 - LER 82-005/03L-0:on 820119,alarm setpoint for radiation monitor RM-LW-108 exceeded Tech Spec limit.Caused by instrument drift.Monitor recalibr. (2 page(s), 2/8/1982)
- ML20041A438 - LER 82-006/03L-0:on 820119,alarm setpoint for radiation monitor RM-GW-102 exceeded Tech Spec limit.Caused by instrument drift.Instrument recalibr. (2 page(s), 2/8/1982)
- ML20041A440 - LER 82-002/03L-0:on 820109,discharge checkvalve of charging svc water pump 2-SW-P-10A found stuck open.Caused by failure of valve disk to reseat properly. (3 page(s), 2/8/1982)