Home > NRC Library > ADAMS Public Documents
Forwards LERs 81-115/01X-2 & 81-115/03L-0.
Accession Number: ML20040B166
Date Released: Sunday, February 23, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20040B165 - Forwards LERs 81-115/01X-2 & 81-115/03L-0. (1 page(s), 1/7/1982)
- ML20040B173 - Forwards LER 81-115/01X-2.Detailed event analysis encl. (3 page(s), 12/9/1981)
- ML20040B180 - LER 81-115/01X-2:on 811125,during routine containment insp, svc water discovered leaking from second from top primary cooling coil on containment fan coil Unit 24.Leak repaired w/Belzona metal filler. (1 page(s), 12/9/1981)
- ML20040B321 - Forwards corrected LER 81-115/03L-0.Detailed event analysis encl. (3 page(s), 12/18/1981)
- ML20040B326 - Corrected LER 81-115/03L-0,on 811120,during normal power, operator received feed flow plus steam flow alarm & noticed steam generator 13 level dropping.Associated bistables tripped;steam flow Channel 2 transmitter replaced. (1 page(s), 12/18/1981)