Home > NRC Library > ADAMS Public Documents
Forwards LERs 81-074/03L-0,81-075/03L-0 & 81-078/03L-0.
Accession Number: ML20039C907
Date Released: Saturday, February 22, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20039C906 - Forwards LERs 81-074/03L-0,81-075/03L-0 & 81-078/03L-0. (1 page(s), 12/23/1981)
- ML20039C912 - LER 81-074/03L-0:on 811126 & 1201,alarm setpoints for component cooling radiation monitors RM-CC-105 & 106 exceeded Tech Spec limit.Caused by fluctuations in component cooling activity.Setpoints reset. (2 page(s), 12/23/1981)
- ML20039C914 - LER 81-075/03L-0:on 811128,sump containing MOV-SW-102A found w/high water level resulting in motor ground.Cause not stated.Valve closed,motor removed,dried & replaced. (2 page(s), 12/23/1981)
- ML20039C916 - LER 81-078/03L-0:on 811206,MOV-LCV-1115E failed to respond properly to train B safety injection signal.Caused by improper wiring connection preventing closing signal from reaching valve.Wiring corrected. (3 page(s), 12/23/1981)