Forwards LERs 82-097/03L-0,82-098/03L-0,82-099/03L-0, 82-100/03L-0 & 82-101/03L-0.
Accession Number: ML20028C263
Date Released: Tuesday, February 11, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20028C262 - Forwards LERs 82-097/03L-0,82-098/03L-0,82-099/03L-0, 82-100/03L-0 & 82-101/03L-0. (1 page(s), 12/22/1982)
- ML20028C266 - LER 82-097/03L-0:on 821204,fire detection sys alarm for 4 kV switchgear room received due to pyralarm detector alarming for no apparent reason.Caused by low setpoint.New detector installed. (1 page(s), 12/4/1982)
- ML20028C270 - LER 82-098/03L-0:on 821127,fire detection sys alarm for 4 kV switchgear room received due to pyralarm detector alarming. Caused by low alarm setpoint.Pyralarm replaced. (1 page(s), 12/22/1982)
- ML20028C278 - LER 82-099/03L-0:on 821123,during surveillance test on automatic load sequence timing relays,four ESF timers found to exceed allowed tolerance.Caused by instrument drift. Timers readjusted & solid state relays under review. (1 page(s), 12/22/1982)
- ML20028C282 - LER 82-100/03L-0:on 821130,during surveillance test on diesel generator load shedding relays,six 4 kV loss of voltage relays exceeded allowed tolerance.Caused by instrument drift.Undervoltage relay under study. (1 page(s), 12/22/1982)
- ML20028C286 - LER 82-101/03L-0:on 821124,discovered time delay of two automatic load sequence relay timers not repeatable & timers exceeded allowed tolerance.Caused by toggle switch assemblies being out of alignment.Assemblies replaced. (1 page(s), 12/22/1982)