Forwards LERs 81-023/03L-0,81-024/03L-0,81-026/03L-0, 81-027/03L-0,81-031/03L-0,81-032/03L-0 & 81-036/03L-0.
Accession Number: ML19346A418
Date Released: Thursday, December 26, 2019
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML19346A417 - Forwards LERs 81-023/03L-0,81-024/03L-0,81-026/03L-0, 81-027/03L-0,81-031/03L-0,81-032/03L-0 & 81-036/03L-0. (1 page(s), 6/12/1981)
- ML19346A420 - LER 81-023/03L-0:on 810425,fuel oil found leaking on diesel generator 1-2A.Caused by failed fuel oil filter gasket. Gasket replaced. (1 page(s), 6/12/1981)
- ML19346A422 - LER 81-024/03L-0:on 810501,high differential pressure across strainer found on diesel generator 1-2A.Caused by excessive accumulation of lube oil sediment/dirt in strainer.Strainer cleaned. (2 page(s), 6/12/1981)
- ML19346A423 - LER 81-026/03L-0:on 810506,on two separate occasions,diesel generator 1C failed to reach rated speed & voltage within required time.Caused by faulty fuel oil check valve.Valve replaced. (2 page(s), 6/12/1981)
- ML19346A424 - LER 81-027/03L-0:on 810429 & 30,injector fuel oil leak found on diesel generator 1-2A.Caused by leaking injector seals. Seals replaced. (1 page(s), 6/12/1981)
- ML19346A425 - LER 81-031/03L-0:on 810506,day tank fuel level on diesel generator 1B found low.Caused by operator error.Tank filled. Operators reinstructed to closely monitor tank level.Design change being evaluated. (2 page(s), 6/12/1981)
- ML19346A426 - LER 81-032/03L-0:on 810508,diesel generator 1C failed to start during operability test.Caused by leaking seal between inner & outer cylinder which allowed water to fill cylinder 10.Cylinder liner replaced. (1 page(s), 6/12/1981)
- ML19346A427 - LER 81-036/03L-0:on 810526,diesel generator 1-2A failed to reach rated speed & voltage within time required.Cause unknown. (1 page(s), 6/12/1981)