- ML19344A698 - Forwards LERs 80-040/03L-0,80-042/03L-0 & 80-043/03L-0. (1 page(s), 8/15/1980)
- ML19344A700 - LER 80-040/03L-0:on 800717,diesel generator 2C was declared inoperable due to tripping,prior to achieving required voltage & frequency upon receipt of low pond level signal. Caused by personnel error.Personnel reinstructed. (2 page(s), 8/15/1980)
- ML19344A701 - LER 80-042/03L-0:on 800801,during QA audit,1B RCP 27-3 & 1C RCP 27-3 undervoltage relay as-found trip values were discovered below Tech Spec limits.Caused by instrument drift.Personnel reinstructed on procedures. (1 page(s), 8/15/1980)
- ML19344A702 - LER 80-043/03L-0:on 800717,diesel generator 1C declared inoperable due to failure to reach rated speed & voltage within required time.Cause is under investigation.Generator was returned to svc.Addl info will be provided. (1 page(s), 8/15/1980)