- ML19341A204 - Forwards LERs 80-113/03L-0,80-114/03L-0 & 80-118/03L-0. (2 page(s), 1/14/1981)
- ML19341A207 - LER 80-113/03L-0:on 801214,during surveillance testing, several penetration fire barriers found lacking seals. Caused not stated.Fire watch posted & openings sealed. (2 page(s), 1/15/1981)
- ML19341A208 - LER 80-114/03L-0:on 801215,during shift channel check of refueling water storage tank,channel C level indicator found reading high.Caused by transmitter zero drift. Transmitter recalibr & returned to svc. (2 page(s), 1/14/1981)
- ML19341A213 - LER 80-118/03L-0:on 801217,during chlorine detection sys surveillance test,101A,B & C detectors electrolyte found not dripping.Caused by vacuums in fluid tanks & clogged glass orifices.Wicks replaced & orifices cleaned. (2 page(s), 1/14/1981)