- ML19208D450 - Forwards LERs 79-058/03X-1,79-076/03L-0 & 79-077/03L-0. (1 page(s), 9/20/1979)
- ML19208D453 - LER 79-058/03X-1:on 790724,as result of analysis of Seismic Category I pipe supports,nine restraints were identified as having safety factor of less than two.As result,reactor bldg sump drain declared inoperable. (1 page(s), 9/20/1979)
- ML19208D461 - LER 79-076/03L-0:on 790821,control room emergency air conditioning unit 2VE1B failed to start.Caused by crankcase oil leak.Leak repaired,oil & freon added. (1 page(s), 9/20/1979)
- ML19208D464 - LER 79-077/03L-0:on 790826,safety injection tank 2T2D level could not be maintained above 80.1% due to makeup valve 2CV-5064 failing to open on command.Caused by improper spring tension on valve operator gate.Tension adjusted. (1 page(s), 9/20/1979)