Forwards LERs 79-068/03L-0,79-067/04L-0,79-064/03L-0 & 79-069/03L-0.
Accession Number: ML19208A101
Date Released: Saturday, August 10, 2019
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML19208A100 - Forwards LERs 79-068/03L-0,79-067/04L-0,79-064/03L-0 & 79-069/03L-0. (1 page(s), 9/5/1979)
- ML19208A102 - LER 79-068/03L-0:on 790812,emergency feedwater flow control valve 2CV-1025-1 from pump 2P7B to steam generator A failed to fully close from control room demand signal.Caused by nonalignment of limit stop switch.Switch realigned. (1 page(s), 9/5/1979)
- ML19208A103 - LER 79-067/04L-0:on 790808,auxiliary bldg radwaste area radiation monitor 2RE-E542 sample pump found w/broken coupling.Cause not stated.Plastic coupling replaced w/metal coupling.Appropriate grab samples taken. (1 page(s), 9/5/1979)
- ML19208A104 - LER 79-064/03L-0:on 790807,trips in plant protection sys D placed in bypass to investigate oscillations in delta-T power indication.Caused by cold leg temp indication oscillation.All related signal connections tightened. (1 page(s), 9/5/1979)