Home > NRC Library > ADAMS Public Documents
Forwards updated LERs 81-007/03X-1,80-037/03X-1 & 80-062/03X-1.
Accession Number: ML18139B300
Date Released: Monday, December 10, 2018
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML18139B299 - Forwards updated LERs 81-007/03X-1,80-037/03X-1 & 80-062/03X-1. (1 page(s), 5/7/1981)
- ML18139B301 - Updated LER 81-007/03X-1:on 810316,w/Unit 1 defueled & 2 at 100% power,power for several radiation monitors lost.Caused by shorting of test lead to ground causing supply fuse to blow.Fuse replaced.Monitors returned to svc. (2 page(s), 5/7/1981)
- ML18139B302 - Updated LER 80-037/03X-1:on 800711,while performing Periodic Test 26.1,radiation monitor RM-SV-111 found inoperative. Caused by spare lug short causing erroneous indications. Lug removed.Monitor returned to svc. (2 page(s), 5/7/1981)
- ML18139B303 - Updated LER-80-062/03X-1:on 801019,w/Unit 1 shutdown & defueled,RM-CC-105 & 106 alarm setpoints found contrary to spec.Caused by decreased background radiation indications. Setpoints reset to value less than twice background. (2 page(s), 5/7/1981)