Forwards nonradiological NPDES permit violation repts for May-Oct 1982.
Accession Number: ML18047A680
Date Released: Saturday, March 21, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML18047A679 - Forwards nonradiological NPDES permit violation repts for May-Oct 1982. (11 page(s), 11/24/1982)
- ML20067B831 - NPDES noncompliance notification:on 821004,max measured TRC value in mixing basin was 0.75 ppm during chlorination of cooling tower A.Caused by excessive chlorine feed for plant conditions.Chlorination terminated. (1 page(s), 10/13/1982)
- ML20067B836 - NPDES noncompliance notification:on 820927,routine weekly sample for oil & grease collected measured 23.0 mg/1. Caused by malfunction of emulsion breaker & oil removal sys. Emulsion breaker oil filters changed. (1 page(s), 10/12/1982)
- ML20067B848 - NPDES noncompliance notification:on 820920,routine weekly oil & grease sample collected measured 123 mg/1.Caused by malfunction of emulsion breaker sys.Emulsion breaker oil filters changed on 820921. (1 page(s), 10/1/1982)
- ML20067B856 - NPDES noncompliance notification:on 820731,daily max limit of 20 mg/1 for oil & grease was exceeded 6 days,resulting in monthly average limit of 15 mg/1 being exceeded.Cause unknown.Oil absorbent pillows changed. (1 page(s), 8/16/1982)
- ML20067B875 - NPDES noncompliance notification:on 820722 & 23,routine oil & grease samples measured 26.5 mg/1 & 31.8 mg/1, respectively.Cause unknown.Oil absorbent pillows changed & floating oil removal devices emptied. (1 page(s), 8/6/1982)
- ML20067B883 - NPDES noncompliance notification:on 820720,routine oil & grease sample indicated 23.5 mg/1 concentration.Cause unknown.Oil absorbent pillows in tank T-41 changed. (1 page(s), 7/30/1982)
- ML20067B887 - NPDES noncompliance notification:on 820712,13 & 14,routine oil & grease samples indicated 21.7 mg/1,25.5 mg/1 & 112.5 mg/1 respectively.Caused by clogged oil removal filters in emulsion breaking sys.Oil filters changed. (1 page(s), 7/22/1982)
- ML20067B893 - NPDES noncompliance notification:on 820628,29 & 30,routine oil & grease samples indicated 37.7 mg/1,23.1 mg/1 & 20.8 mg/1,respectively.Caused by malfunction of oil treatment skid & associated equipment.Oil removal filters changed. (3 page(s), 7/7/1982)