- ML18045A242 - Forwards LERs 80-014/03L-0,80-015/03L-0,80-016/03L-0 & 80-017/03L-0. (1 page(s), 6/13/1980)
- ML18045A244 - LER 80-014/03L-0:on 800512,during routine testing of hydraulic snubbers,oil level in snubber 5 found to be less than zero.Caused by rust combined w/vibrator,accelerating seal failure.Rust found inside accumalator. (1 page(s), 6/13/1980)
- ML18045A245 - LER 80-015/03L-0:on 800512,during routine testing of hydraulic snubber,oil level in snubber 9 found to be less than zero.Cause of seal damage unknown;normal wear suspected.Accumulator plunger seal found to be damaged. (1 page(s), 6/13/1980)
- ML18045A247 - LER 80-016/03L-0:on 800515,during testing of hydraulic snubber,oil level in snubber 7 found to be less than zero. Caused by seal degradation.Snubber will be disassembled to confirm cause. (1 page(s), 6/13/1980)