Home > NRC Library > ADAMS Public Documents
Forwards updated LERs 78-065/03X-1,79-022/03X-1, 79-030/03X-1,79-038/03L-0 & 79-039/03L-0.
Accession Number: ML17317B468
Date Released: Friday, September 20, 2019
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML17317B467 - Forwards updated LERs 78-065/03X-1,79-022/03X-1, 79-030/03X-1,79-038/03L-0 & 79-039/03L-0. (17 page(s), 8/15/1979)
- ML17317B471 - Updated LER 78-065/03X-1 on 781229:previous rept of inoperable pressurizer level channel is no longer considered RO due to recent Tech Spec change deleting all pressurizer low level operability requirements. (2 page(s), 8/15/1979)
- ML17317B473 - Updated LER 79-022/03X-1 on 790323:to prevent recurrence of nearly simultaneous bus failures,battery equalizing charge has been reduced from 280 to 275 volts.Addl design change requested to provide overvoltage alarm to alert operators. (2 page(s), 8/15/1979)
- ML17317B474 - Updated LER 79-030/03X-1 on 790417:design change coupled w/relay degradation caused relay to react slower during sequence.Design change RFC-DC-12-2384 installed as preventive measure. (2 page(s), 8/15/1979)
- ML19249A279 - Updated LER 79-038/03L-0 on 790717:engineering review in progress to determine cause of recurring problem of indicated position of control rods N-13 & H-6 exceeding Tech Specs. (2 page(s), 8/15/1979)