Home > NRC Library > ADAMS Public Documents
Forwards LERs 80-002/03L-0,80-003/03L-0 & 80-004/03L-0.
Accession Number: ML111720996
Date Released: Thursday, September 1, 2011
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML111720995 - Forwards LERs 80-002/03L-0,80-003/03L-0 & 80-004/03L-0. (2 page(s), 2/15/1980)
- ML111720997 - LER 80-004/03L-0:on 800117,while diesel generator 1B was supplying emergency power following auxiliary transformer failure,lube oil was added to D/G air box.Caused by air box being painted w/TM oil sys color code. (3 page(s), 2/15/1980)
- ML111720998 - LER 80-002/03L-0:on 800117,during full power operation,fault occurred in reserve auxiliary transformer.Caused by internal bushing failure.Transformer was repaired & returned to svc. (2 page(s), 2/15/1980)
- ML111720999 - LER 80-003/03L-0:on 800117,following reserve auxiliary transformer failure,condensate water storage tank inventory decreased below Tech Specs.Caused by steam dumping operations for RCS temp control. (2 page(s), 2/15/1980)