Forwards AO-5-2-8(B),AO-5-2-9(B) & AO-5-2-10(B).
Accession Number: ML093561144
Date Released: Tuesday, June 1, 2010
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML093561143 - Forwards AO-5-2-8(B),AO-5-2-9(B) & AO-5-2-10(B). (2 page(s), 6/20/1975)
- ML093561146 - AO-5-2-8(B):on 750522,pump 21 removed from svc to repair seal heat exchanger drip.Caused by Ingersoll-Rand model pump leak at pump seal heat exchanger screwed fitting.Fittings disassembled & reassembled. (1 page(s), 6/20/1975)
- ML093561147 - AO-5-2-9(B):on 750524,observed that loop 24 overpower delta temp setpoint was drifting.Caused by Foxboro summing amplifier w/poor wipe on summing potentiometers.Pots replaced. (1 page(s), 6/20/1975)
- ML093561148 - AO-5-2-10(B):on 750526,condensate storage tank level allowed to drop below Tech Spec limit.Caused by output of flash evaporator,normal supply of makeup,being reduced due to out of spec water.Water returned to spec. (2 page(s), 6/20/1975)