EA-05-190 - Indian Point 2 & 3(Entergy Nuclear Operations, Inc.)
EA-05-190
January 31, 2006
Mr. Michael R. Kansler
President
Entergy Nuclear Operations, Inc.
440 Hamilton Avenue
White Plains, NY 10601
| SUBJECT: | CONFIRMATORY ORDER MODIFYING LICENSE TO REQUIRE BACKUP POWER FOR THE EMERGENCY NOTIFICATION SYSTEM FOR INDIAN POINT NUCLEAR GENERATING UNIT NOS. 2 AND 3 |
Dear Mr. Kansler:
The U.S. Nuclear Regulatory Commission (NRC or the Commission) is issuing the enclosed Confirmatory Order to Entergy Nuclear Operations, Inc., to address the requirement of PL 109-58, 119 Stat 594, Section 651(b) of the Energy Policy Act (Act) of 2005. The Act was enacted on August 8, 2005. The Act mandates that “for any licensed nuclear power plants located where there is a permanent population, as determined by the 2000 decennial census, in excess of 15,000,000 within a 50-mile radius of the power plant, not later than 18 months after enactment of this Act, the Commission shall require that backup power to be available for the emergency notification system of the power plant, including the emergency siren warning system, if the alternating current supply within the 10-mile emergency planning zone of the power plant is lost.” Indian Point Nuclear Generating Unit Nos. 2 and 3 meet the criteria of the Act. The Confirmatory Order will require backup power for the emergency notification system used for Indian Point Nuclear Generating Unit Nos. 2 and 3. The Confirmatory Order will become effective immediately upon issuance and fully implemented by January 30, 2007.
Questions concerning this Confirmatory Order should be addressed to Eric J. Leeds, Director, Division of Preparedness and Response, who can be reached at (301) 415-2334 or Nader L. Mamish, Director, Emergency Preparedness Directorate, who can be reached at (301) 415-1086.
Pursuant to Section 223 of the Atomic Energy Act of 1954, as amended, any person who willfully violates, attempts to violate, or conspires to violate, any provision of this Order shall be subject to criminal prosecution as set forth in that section. Violation of this Order may also subject the person to civil monetary penalty.
In accordance with Title 10 of the Code of Federal Regulations, Section 2.390 of the NRC’s “Rules of Practice,” a copy of this letter and its enclosure will be available electronically for public inspection in the NRC Public Document Room or from the publicly available record component of the NRC’s Agencywide Documents Access and Management System (ADAMS).
ADAMS is accessible from the NRC website at http://www.nrc.gov/reading-rm/adams.html
(Public NRC Library). To the extent possible, your response
should not include any personal privacy, proprietary, or safeguards
information so that it can be made available to the Public without
redaction. The NRC also includes significant enforcement actions
on its Web site at www.nrc.gov; select What
We Do, Enforcement, then
Significant
Enforcement Actions.
| Sincerely, |
|
| /RA/ |
|
| J. E. Dyer, Director Office of Nuclear Reactor Regulation |
Docket Nos. 50-247 and 50-286
Enclosure: As stated
cc:
| Mr. Gary J. Taylor Chief Executive Officer Entergy Operations, Inc. 1340 Echelon Parkway Jackson, MS 39213 |
Ms. Charlene D. Faison Manager, Licensing Entergy Nuclear Operations, Inc. 440 Hamilton Avenue White Plains, NY 10601 |
| Mr. John T. Herron Senior Vice President and Chief Operating Officer Entergy Nuclear Operations, Inc. 440 Hamilton Avenue White Plains, NY 10601 |
Mr. Michael J. Columb Director of Oversight Entergy Nuclear Operations, Inc. 440 Hamilton Avenue White Plains, NY 10601 |
| Mr. Fred R. Dacimo Site Vice President Entergy Nuclear Operations, Inc. Indian Point Energy Center 295 Broadway, Suite 1 P.O. Box 249 Buchanan, NY 10511-0249 |
Mr. James Comiotes Director, Nuclear Safety Assurance Entergy Nuclear Operations, Inc. Indian Point Energy Center 295 Broadway, Suite 1 P.O. Box 249 Buchanan, NY 10511-0249 |
| Mr. Paul Rubin General Manager, Plant Operations Entergy Nuclear Operations, Inc. Indian Point Energy Center 295 Broadway, Suite 2 P.O. Box 249 Buchanan, NY 10511-0249 |
Mr. Patric Conroy Manager, Licensing Entergy Nuclear Operations, Inc. Indian Point Energy Center 295 Broadway, Suite 1 P. O. Box 249 Buchanan, NY 10511-0249 |
| Mr. Oscar Limpias Vice President Engineering Entergy Nuclear Operations, Inc. 440 Hamilton Avenue White Plains, NY 10601 |
Mr. Travis C. McCullough Assistant General Counsel Entergy Nuclear Operations, Inc. 440 Hamilton Avenue White Plains, NY 10601 |
| Mr. Brian O’Grady Vice President, Operations Support Entergy Nuclear Operations, Inc. 440 Hamilton Avenue White Plains, NY 10601 |
Ms. Stacey Lousteau Treasury Department Entergy Services, Inc. 639 Loyola Avenue Mail Stop: L-ENT-15E New Orleans, LA 70113 |
| Mr. John F. McCann Director, Licensing Entergy Nuclear Operations, Inc. 440 Hamilton Avenue White Plains, NY 10601 |
Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 |
| Senior Resident Inspector’s Office Indian Point 2 U. S. Nuclear Regulatory Commission P.O. Box 59 Buchanan, NY 10511 |
Mr. William DiProfio PWR SRC Consultant 139 Depot Road East Kingston, NH 03827 |
| Senior Resident Inspector’s Office Indian Point 3 U. S. Nuclear Regulatory Commission P.O. Box 59 Buchanan, NY 10511 |
Mr. Daniel C. Poole PWR SRC Consultant P.O. Box 579 Inglis, FL 34449 |
| Mr. Peter R. Smith, President New York State Energy, Research, and Development Authority 17 Columbia Circle Albany, NY 12203-6399 |
Mr. William T. Russell PWR SRC Consultant 400 Plantation Lane Stevensville, MD 21666-3232 |
| Mr. Paul Eddy Electric Division New York State Department of Public Service 3 Empire State Plaza, 10th Floor Albany, NY 12223 |
Mr. Jim Riccio Greenpeace 702 H Street, NW Suite 300 Washington, DC 20001 |
| Mr. Charles Donaldson, Esquire Assistant Attorney General New York Department of Law 120 Broadway New York, NY 10271 |
Mr. Phillip Musegaas Riverkeeper, Inc. 828 South Broadway Tarrytown, NY 10591 |
| Mayor, Village of Buchanan 236 Tate Avenue Buchanan, NY 10511 |
Mr. Mark Jacobs IPSEC 46 Highland Drive Garrison, NY 10524 |
| Mr. Ray Albanese Executive Chair Four County Nuclear Safety Committee Westchester County Fire Training Center 4 Dana Road Valhalla, NY 10592 |
7590-01-P
UNITED STATES OF AMERICA
NUCLEAR REGULATORY COMMISSION
| In the Matter of | ) |
Docket Nos. 50-247 and 50-286 |
| ENTERGY NUCLEAR OPERATIONS, INC. | ) |
License Nos. DPR-26 and DPR |
| (Indian Point Nuclear Generating Unit Nos. 2 and 3) |
) ) |
EA-05-190 |
CONFIRMATORY ORDER MODIFYING LICENSE
(EFFECTIVE IMMEDIATELY)
I
Entergy Nuclear Operations, Inc. (Licensee) is the holder of Facility Operating License Nos. DPR-26 and DPR-64 issued by the Nuclear Regulatory Commission (NRC or Commission) pursuant to 10 CFR Part 50. The licenses authorize the operation of Indian Point Nuclear Generating Unit Nos. 2 and 3, in accordance with the conditions specified therein. The facilities are located on the Licensee’s site in Buchanan, New York.
II
The Energy Policy Act of 2005 (Act) (see 42 U.S.C. 2210 et seq.) was enacted on August 8, 2005. Section 651(b) of the Act states:
“For any licensed nuclear power plants located where there is a permanent population, as determined by the 2000 decennial census, in excess of 15,000,000 within a 50-mile radius of the power plant, not later than 18 months after enactment of this Act, the Commission shall require that backup power to be available for the emergency notification system of the power plant, including the emergency siren warning system, if the alternating current supply within the 10-mile emergency planning zone of the power plant is lost.”
PL 109-58, 119 Stat 594. Indian Point Nuclear Generating Unit Nos. 2 and 3 meet the criteria of the Act.
Adequate backup power for the emergency notification system (ENS), as required by Section 651(b) of the Act, requires that: (a) the backup power supply for the Public Alerting System (PAS) must meet commonly-applicable standards, such as National Fire Protection Association (NFPA) Standard 1221, Standard for the Installation, Maintenance, and Use of Emergency Communications Systems (2002) and Underwriters Laboratory (UL) 2017, Section 58.2; (b) each PAS and PAS Alerting Appliance (PASAA) must receive adequate power to perform their intended functions such that backup power is sufficient to allow operation in standby mode for a minimum of 24 hours and in alert mode for a minimum of 15 minutes; (c) batteries used for backup power must recharge to at least 80 percent of their capacity in no less than 24 hours; (d) except for those components that are in facilities staffed on a continuous basis (24 hours per day, 7 days per week) or otherwise monitored on a continuous basis, immediate automatic indication of a loss of power must be provided to the Licensee and appropriate government agencies; and (e) except for those components that are in facilities staffed on a continuous basis (24 hours per day, 7 days per week) or otherwise monitored on a continuous basis, an automatic notification of an unplanned loss of power must be made to the Licensee in sufficient time to take compensatory action before the backup power supply can not meet the requirements of Section IV, part II. A. 2.
III
In order to carry out the statutory mandate discussed above, the Commission has determined that the operating licenses for Indian Point Nuclear Generating Unit Nos. 2 and 3 must be modified to include provisions with respect to the measures identified in Section II of this Order. The requirements needed to effectuate the foregoing are set forth in Section IV below. On January 31, 2006, the Licensee consented to the license modifications set forth in Section IV below. The Licensee further agreed in its letter dated January 31, 2006, that it has waived its right to a hearing on this Order, and, therefore, that the terms of the Order are effective upon issuance.
I find that the license modifications set forth in Section IV are acceptable and necessary, and conclude that with these provisions the Licensee will be in compliance with the intent of the Act. Based on the above and Licensee’s consent, this Order is immediately effective upon issuance.
IV
Accordingly, pursuant to Sections 104b, 161b, 161i, 161o, 182 and 186 of the Atomic Energy Act of 1954, as amended, Section 651(b) of the Energy Policy Act of 2005 (PL 109-58, 119 Stat 594), and the Commission’s regulations in 10 CFR 2.202 and 10 CFR Part 50, IT IS HEREBY ORDERED, EFFECTIVE IMMEDIATELY, THAT LICENSE NOS. DPR-26 AND DPR-64 ARE MODIFIED AS FOLLOWS:
| I. | The Licensee shall provide and maintain a backup power
supply for the ENS for the Indian Point Nuclear Generating Unit Nos.
2 and 3, facilities. The ENS is the primary prompt notification system
used to alert the public of an event at a nuclear power plant. |
||
| II. | The Licensee shall implement II.A, II.B, and II.C.1-3 by January
30, 2007. The backup power system for the ENS shall be declared operable
by January 30, 2007. The backup power supply for the ENS shall include,
as a minimum: |
||
| A. | 1. | A backup power supply for the PAS and each PASAA which
shall provide adequate power for each component to perform their design
function. These functions include the following as examples: sound
output, rotation, speech intelligibility, or brightness as applicable.
This criterion includes the associated activation, control, monitoring,
and testing components for the backup power supply to the ENS including,
but not limited to: radio transceivers, testing circuits, sensors to
monitor critical operating parameters of the PAS and PASAA. The Licensee is required to meet all applicable standards, such as NFPA Standard 1221, Standard for the Installation, Maintenance, and Use of Emergency Communications Systems (2002) and UL 2017, Section 58.2; |
|
| 2. | The backup power supply for each PAS and PASAA shall be designed for
operation in standby mode, including, but not limited to: radio transceivers,
testing circuits, sensors fully operational and providing polling data
to the activation, control, monitoring, and test system for at least
24 hours without AC supply power from the local electric distribution
grid. The backup power supply then shall be capable of performing its
intended function, without recharge, by operating the PAS and PASAA in
its alerting mode at its full design capability for a period of at least
15 minutes. This sequence shall be assumed to occur at the most unfavorable
environmental conditions including, but not limited to, temperature,
wind, and precipitation specified for PAS and PASAA operation and assume
that the batteries are approaching the end of their design life (i.e.,
the ensuing recharge cycle will bring the batteries back to the minimum
state that defines their design life). |
||
| 3. | In defining battery design life, automatic charging shall be sized
such that batteries in the backup power are fully recharged to at least
80 percent of their maximum rated capacity from the fully discharged
state in a period of not more than 24 hours. |
||
| 4. | Battery design life and replacement frequency shall comply with vendor(s)
recommendations. |
||
| 5. | Except for those components that are in facilities staffed on a continuous
basis (24 hours per day, 7 days per week) or otherwise monitored on a continuous
basis, there shall be a feedback system(s) that provides immediate automatic
indication of a loss of power to the Licensee and the appropriate government
agencies, and an automatic notification of an unplanned loss of power must
be made to the Licensee in sufficient time to take compensatory action before
the backup power supply can not meet the requirements of Section IV, part II.
A. 2. |
||
| 6. | The Licensee shall implement a preventative maintenance and testing
program of the ENS including, but not limited to: the equipment that
activates and monitors the system, equipment that provides backup power,
and the alerting device to ensure the ENS system performs to its design
specifications. |
||
| B. | 1. | The Licensee shall implement any new Department of Homeland Security
(DHS) guidance pertaining to backup power for ENS that may affect the
system requirements outlined in this Order that is issued prior to obtaining
DHS approval of the alerting system design. The Licensee shall not implement
any DHS guidance that reduces the effectiveness of the ENS as provided
for in this Order without prior NRC approval. |
|
| 2. | The Licensee shall document the evaluation of lessons learned from
any evaluation of the current alert and notification system (ANS) and
address resolution of identified concerns when designing the backup power
system and such consideration shall be included in the design report. |
||
| 3. | The final PAS design must be submitted to DHS for approval prior to
May 1, 2006. |
||
| C. | 1. | Within 60 days of the issuance of this Order, the Licensee shall submit
a response to this Order to the NRC Document Control Desk providing a
schedule of planned activities associated with the implementation of
the Order including interactions with the Putnam, Rockland, Westchester,
and Orange Counties, the State of New York, and DHS. In addition, the
Licensee shall provide a progress report on or shortly before June 30,
2006. |
|
| 2. | The Licensee shall submit a proposed revision to its emergency response
plan to incorporate the implementation of items A.1–A.6, B.1–B.3,
and C.4–C.5. This plan shall be submitted to the NRC for review
and approval within 120 days from the issuance of the Order. |
||
| 3. | Prior to declaring the ENS operable, the Licensee shall, in accordance
with a test plan submitted to and approved by the NRC in conjunction
with the design submittal, demonstrate satisfactory performance of all
(100%) of the ENS components including the ability of the backup power
supply to meet its design requirements. |
||
| 4. | After declaring the ENS operable, the Licensee shall conduct periodic
testing to demonstrate reliable ENS system performance. |
||
| 5. | The results from testing as discussed in paragraph C.4 shall be reported,
in writing, to the NRC Document Control Desk, with a copy to the Director
of Nuclear Reactor Regulation, documenting the results of each test,
until there are 3 consecutive tests testing the operability of all ENS
components used during an actual activation), conducted no sooner than
25 days and no more than 45 days from the previous test with a 97% overall
entire emergency planning zone success rate with no individual county
failure rate greater than 10%. A false negative report from a feedback
system will constitute a siren failure for the purposes of this test. |
||
| III. | The Licensee shall submit a written report to the NRC Document
Control Desk, with a copy to the Director of Nuclear Reactor Regulation,
when the ENS is declared operable. |
||
| IV. | The Licensee shall submit a written report to the NRC Document
Control Desk and provide a copy to the Director of Nuclear Reactor Regulation
when it has achieved full compliance with the requirements contained
in this Order. |
||
| V. | The Licensee may use the criteria contained in 10 CFR 50.54(q) to make changes to the requirements contained in this Order without prior NRC approval provided that they do not reduce the effectiveness of the Order requirements or the approved emergency plan. The Licensee shall notify, in writing, the NRC Document Control Desk, with a copy to the Director, Division of Preparedness and Response, Office of Nuclear Security and Incident Response, 30 days in advance of implementing such a change. For other changes, the Licensee may submit a request, in writing, to the NRC Document Control Desk, with a copy to the Director, Office of Nuclear Reactor Regulation, to relax or rescind any of the above requirements upon a showing of good cause by the Licensee. | ||
V
Any person adversely affected by this Confirmatory Order, other than the
Licensee, may request a hearing within 20 days of its issuance. Where good
cause is
shown, consideration will be given to extending the time to request a hearing.
A request for extension of time must be made in writing to the Director,
Office of Nuclear Reactor Regulation, U.S. Nuclear Regulatory Commission,
Washington, D.C. 20555, and include a statement of good cause for the extension.
Any request for a hearing shall be submitted to the Secretary, U.S. Nuclear
Regulatory Commission, ATTN: Chief, Rulemakings and Adjudications Staff,
Washington, D.C. 20555. Copies of the hearing request shall also be sent
to the Director, Office of Nuclear Reactor Regulation, U.S. Nuclear Regulatory
Commission, Washington, D.C. 20555; to the Assistant General Counsel for
Materials Litigation and Enforcement at the same address; to the Regional
Administrator, NRC Region I, U.S. NRC Region I, 475 Allendale Road, King
of Prussia, PA 19406-1415; and to the Licensee, Entergy Nuclear Operations,
Inc., 440 Hamilton Avenue, White Plains, NY 10601. Because of continuing
disruptions in delivery of mail to United States Government offices, it
is requested that answers and requests for hearing or for time extensions
be
transmitted to the Secretary of the Commission either by means of facsimile
transmission to 301-415-1101, or by e-mail to hearing.docket@nrc.gov, and
also to the Office of the General Counsel either by means of facsimile
transmission to 301-415-3725 or by e-mail to OGCMailCenter.Resource@nrc.gov. If a
person other
than the Licensee requests a hearing, that person shall set forth with
particularity the manner in which his interest is adversely affected by this
Order and
shall address the criteria set forth in 10 CFR 2.309.
If the hearing is requested by a person whose interest is adversely affected,
the Commission will issue an Order designating the time and place of any
hearing. If a hearing is held, the issue to be considered at such hearing
shall be whether
this Confirmatory Order should be sustained.
In the absence of any request for hearing or written approval of an extension
of time in which to request a hearing, the provisions specified in Section
IV above shall be final 20 days from the date of this Order without further
order or proceedings. If an extension of time for requesting a hearing has
been approved, the provisions specified in Section IV shall be final when
the extension expires if a hearing request has not been received. AN ANSWER
OR
A REQUEST FOR HEARING SHALL NOT STAY THE IMMEDIATE EFFECTIVENESS OF THIS
ORDER.
| FOR THE NUCLEAR REGULATORY COMMISSION |
|
| /RA/ |
|
| J. E. Dyer, Director Office of Nuclear Reactor Regulation |
Dated this 31st day of January 2006