United States Nuclear Regulatory Commission - Protecting People and the Environment
Home > NRC Library > Document Collections > Reports Associated with Events > Event Notification Reports > 2020 > August 05

Event Notification Report for August 05, 2020

U.S. Nuclear Regulatory Commission
Operations Center

Event Reports For
8/4/2020 - 8/5/2020

** EVENT NUMBERS **


54778 54802 54812 54816

To top of page
Agreement State Event Number: 54778
Rep Org: CALIFORNIA RADIATION CONTROL PRGM
Licensee: RMA Group
Region: 4
City: Rancho Cucamonga   State: CA
County:
License #: 071420
Agreement: Y
Docket:
NRC Notified By: L. Robert Greger
HQ OPS Officer: Ossy Font
Notification Date: 07/14/2020
Notification Time: 23:51 [ET]
Event Date: 07/13/2020
Event Time: 06:00 [PDT]
Last Update Date: 07/15/2020
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
VINCENT GADDY (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB (EMAIL)
- CNSNS (MEXICO) (EMAIL)
This material event contains a "Less than Cat 3" level of radioactive material.

Event Text

AGREEMENT STATE REPORT - STOLEN MOISTURE DENSITY GAUGE

The following was received from the California Department of Public Health via email:

"A Troxler moisture density gauge (model 3430, serial # 31716) was reported stolen Monday morning at approximately 0600 PDT from the bed of an employee's vehicle while the vehicle was parked for 1-2 hours outside the employee's residence in Moreno Valley, CA. The gauge contains approximately 0.3 GBq (8 mCi) of Cs-137 and 1.50 GBq (40 mCi) of Am-241. The gauge was reportedly picked up earlier that morning at the licensee's office in Rancho Cucamonga, and left appropriately chained/locked in the back of the vehicle at the employee's residence before leaving for a work location. The theft was reported to the Moreno Valley Police Department (police report #MV201950058 taken by Officer Flores). A reward will be advertised for the return of the gauge."

California 5010 NUMBER: 071420

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf

To top of page
Agreement State Event Number: 54802
Rep Org: FLORIDA BUREAU OF RADIATION CONTROL
Licensee: Unknown
Region: 1
City: Jacksonville   State: FL
County:
License #:
Agreement: Y
Docket:
NRC Notified By: David Pieski
HQ OPS Officer: Kerby Scales
Notification Date: 07/27/2020
Notification Time: 13:05 [ET]
Event Date: 07/27/2020
Event Time: 00:00 [EDT]
Last Update Date: 07/27/2020
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
BRICE BICKETT (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB (EMAIL)

Event Text

AGREMENT STATE REPORT - TROXLER GAUGE ON EBAY

The following was received from the Florida Bureau of Radiation Control (BRC) via email:

The RSO [Radiation Safety officer] of Laboratory Technical Services, Milton, FL (License number 3734-1) contacted this office [BRC] at 1200 [EDT] to report a model 3450 Troxler Gauge inappropriately advertised on ebay. The Troxler location is advertised in Jacksonville, FL. Acting IRC [Incident Response Coordinator] contacted ebay at 1237 to report the prohibited item.

Florida Incident Number: FL20-086

To top of page
Power Reactor Event Number: 54812
Facility: Brunswick
Region: 2     State: NC
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: Benjamin Williams
HQ OPS Officer: Bethany Cecere
Notification Date: 08/03/2020
Notification Time: 23:31 [ET]
Event Date: 08/03/2020
Event Time: 23:12 [EDT]
Last Update Date: 08/04/2020
Emergency Class: Unusual Event
10 CFR Section:
50.72(a) (1) (i) - Emergency Declared
50.72(b)(2)(iv)(B) - RPS Actuation - Critical
50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation
Person (Organization):
MARK MILLER (R2DO)
LAURA DUDES (R2 RA)
HO NIEH (NRR)
SILAS KENNEDY (IRD)
CHRIS MILLER (NRR EO)
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 20 Power Operation 0 Hot Shutdown

Event Text

UNUSUAL EVENT DECLARED DUE TO A LOSS OF OFFSITE POWER

At 2312 EDT, on August 4, 2020, Brunswick Unit 1 declared an Unusual Event due to a loss of offsite power. The unit was at approximately 20 percent power and was not synced to the grid when the unit automatically scrammed. All control rods fully inserted. Emergency Diesel Generators started and began powering the safety buses. Safety systems actuated as expected.

The Unit also experienced a loss of Fuel Pool Cooling and Cleanup System, but one pump was returned to service.

Unit 2 remains at 100 percent power and is unaffected.

The licensee notified State and local governments, as well as the NRC Resident Inspector.

Notified DHS SWO, FEMA Operations Center, CISA IOCC, FEMA NWC (email), DHS Nuclear SSA (email), and FEMA NRCC SASC (email).


* * * UPDATE FROM MARK TURKAL TO DONALD NORWOOD AT 0120 EDT ON 8/4/2020 * * *

"At approximately 2302 EDT, a loss of offsite power occurred on Unit 1. This resulted in a Reactor Protection System (RPS) actuation. Per design, emergency diesel generators 1 and 2 properly started and loaded to their respective emergency buses. The Reactor Core Isolation Cooling (RCIC) system was manually started and is being used to control reactor water level. The High Pressure Coolant Injection (HPCI) system was manually started and is being used for pressure control. As previously reported, an Unusual Event was declared at 2312 EDT due to the loss of offsite power. At the time of the event, Unit 1 was in the process of shutting down for maintenance associated with a ground on the main generator.

"Due to the RPS actuation while critical, this event is being reported as a four-hour, nonemergency notification per 10 CFR 50.72(b)(2)(iv)(B).

"As a result of the reactor trip, reactor water level reached low level 1 (LL1). The LL1 signal causes a Group 2 (i.e., floor and equipment drain isolation valves), Group 6 (i.e., monitoring and sample isolation valves) and Group 8 (i.e., shutdown cooling isolation valves) isolations. The LL1 isolations occurred as designed; the Group 8 valves were closed at the time of the event. Per design, the loss of offsite power also caused a Group 1 (i.e., main steam isolation valve) isolations.

"Due to the Emergency Diesel Generator and Primary Containment Isolation System (PCIS) actuations, this event is also being reported as an eight-hour, nonemergency notification in accordance with 10 CFR 50.72(b)(3)(iv)(A).

"Unit 2 was not affected. There was no impact to the health and safety of the public or plant personnel. The safety significance of the event is minimal. All safety related systems operated as designed.

"Investigation of the cause of the loss of offsite power is in progress."

The licensee notified the NRC Resident Inspector. Notified R2DO (Inverso).

To top of page
Power Reactor Event Number: 54816
Facility: Millstone
Region: 1     State: CT
Unit: [] [2] []
RX Type: [1] GE-3,[2] CE,[3] W-4-LP
NRC Notified By: Michael Watson
HQ OPS Officer: Andrew Waugh
Notification Date: 08/04/2020
Notification Time: 22:43 [ET]
Event Date: 08/04/2020
Event Time: 17:45 [EDT]
Last Update Date: 08/04/2020
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(3)(v)(A) - Pot Unable To Safe Sd
50.72(b)(3)(v)(B) - Pot Rhr Inop
50.72(b)(3)(v)(D) - Accident Mitigation
Person (Organization):
FRANK ARNER (R1DO)
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 75 Power Operation

Event Text

BOTH SERVICE WATER HEADERS DECLARED INOPERABLE

On 8/4/20, at 1745 EDT, Millstone Unit 2 entered technical specification (TS) 3.0.3 due to both service water headers being declared inoperable because strainer differential pressures (D/Ps) were greater than 9 psid. The high service water strainer D/P was the result of heavy debris impingement caused by tropical storm Isaias. To reduce heat loads and service water flow, Unit 2 reduced power to 75 percent.

One service water header was restored to operable at 1816 EDT, at which time TS 3.0.3 was exited. At 1843 EDT both service water headers were declared operable.

The NRC Resident Inspector has been notified.


Page Last Reviewed/Updated Wednesday, August 05, 2020
Wednesday, August 05, 2020