Design-Specific Review Standard (DSRS) for the mPower™ Design - Chapter 8

This page includes links to files in non-HTML format. See Plugins, Viewers, and Other Tools for more information.

NUREG-0800 SRP/DSRS Section No. NUREG-0800 SRP/DSRS Section Title Applicability of NUREG-0800 Section to mPower™ Design Comments/Additional Guidance Documents to be used for Review, etc.
8.1
ML12269A005
Electric Power - Introduction C) Modify SRP Section for DSRS  
8.2
ML12269A006
Offsite Power System C) Modify SRP Section for DSRS  
8.3.1
ML12269A010
AC Power Systems (Onsite) C) Modify SRP Section for DSRS  
8.3.2
ML12269A011
DC Power Systems (Onsite) C) Modify SRP Section for DSRS  
8.4
ML12269A015
Station Blackout C) Modify SRP Section for DSRS  
8-A General Agenda, Station Site Visits B) Delete SRP Section for DSRS (N/A)  
BTP 8-1
ML070710423
Requirements on Motor-operated Valves in the ECCS Accumulator Lines A) Use SRP Section "as-is" (minor comments)  
BTP 8-2
ML12269A016
Use of Diesel-Generator Sets for Peaking C) Modify SRP Section for DSRS  
BTP 8-3
ML12269A017
Stability of Offsite Power Systems C) Modify SRP Section for DSRS  
BTP 8-4
ML070710452
Application of the Single Failure Criterion to Manually Controlled Electrically Operated Valves A) Use SRP Section "as-is" (minor comments)  
BTP 8-5 Supplemental Guidance for Bypass and Inoperable Status Indication for Engineered Safety Features Systems B) Delete SRP Section for DSRS (N/A)  
BTP 8-6
ML12269A018
Adequacy of Station Electric Distribution System Voltages C) Modify SRP Section for DSRS  
BTP 8-7 Criteria for Alarms and Indications Associated with Diesel-Generator Unit Bypassed and Inoperable Status B) Delete SRP Section for DSRS (N/A)  