Home > NRC Library > ADAMS Public Documents
Forwards LERs 86-001-00,86-003-00,86-004-00 & 86-005-00.
Accession Number: ML20197A548
Date Released: Wednesday, July 29, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20197A544 - Forwards LERs 86-001-00,86-003-00,86-004-00 & 86-005-00. (2 page(s), 10/23/1986)
- ML20197A562 - LER 86-001-00:on 860930,RWCU Pump Room 3 temp high annunciator alarmed in main control room.Probably caused by grounds in temp module coincident w/thermocouple grounds. Ground corrected. (3 page(s), 10/23/1986)
- ML20197A587 - LER 86-003-00:on 860930,control room ventilation sys Train B shifted to high chlorine mode of operation.Caused by broken detector tape in chlorine detector due to excess spring tension causing excessive drag on tape.Tape rethreaded. (3 page(s), 10/23/1986)
- ML20197A706 - LER 86-004-00:on 861001,automatic initiation of standby gas treatment sys occurred following containment fuel transfer vent plenum high radiation signal.Caused by personnel error & faulty procedures. (3 page(s), 10/23/1986)
- ML20197A754 - LER 86-005-00:on 861007,firewatch rounds for impaired barriers started late.Caused by personnel negligence. Contract employee suspended & subsequently resigned. (3 page(s), 10/23/1986)