Material Transport Analysis for Accident-Induced Flow in Nuclear Facilities (NUREG/CR-3527, LA-9913-MS)
On this page:
Download complete document
This page includes links to files in non-HTML format. See Plugins, Viewers, and Other Tools for more information.
Publication Information
Manuscript Completed: September 1983
Date Published: October 1983
Prepared by:
R.A. Martin, P.K. Tang, A.P. Harper, J.D. Novat, W.S. Gregory
Los Alamos National Laboratory
Los Alamos, New Mexico 87545
Prepared for:
Division of Risk Analysis
Office of Nuclear Regulatory Research
U.S. Nuclear Regulatory Commission
Washington, DC 20555-0001
NRC FIN A-7029
Abstract
This report is a summary of the material transport modeling procedures developed to support a family of accident analysis computer codes. The material transport modeling areas include transport initiation, convection, interaction, depletion, and filtration. Except for material interaction, these areas are developed in modular form in three Los Alamos National Laboratory computer codes: TORAC, EXPAC, and FIRAC. This family of codes was developed to provide improved methods of tornado, explosion, and fire accident consequence assessment, respectively, for the 'nuclear industry. Although the codes were designed to estimate accident-induced gas-dynamic, thermal, and material transport transient phenomena in nuclear fuel cycle facility ventilation systems, they are applicable to other facilities as well. Sample problems using TORAC have been provided to illustrate the current material transport capabilities for a simple system under tornado-induced accident conditions. Some suggestions for future improvements to some of these material transport models also are discussed.