Test and Criteria for Fire Protection of Cable Penetrations (NUREG/CR-2377, SAND81-7160)
On this page:
Download complete document
This page includes links to files in non-HTML format. See Plugins, Viewers, and Other Tools for more information.
Publication Information
Manuscript Completed: June 1981
Date Published: October 1981
Prepared by:
Robert Brady Williamson, Principa! Investigator
Fred L. Fisher, Senior Development Engineer
Lawrence Berkeley Laboratory
University of California
Berkeley, California 94720
Under Sandia Contract No. 13-7331
for Sandia National Laboratories
Albuquerque, New Mexico 87185
Operated by Sandia Corporation
for the U.S. Department of Energy
L.J. Klamerus, Sandia Project Officer
Prepared for:
Division of Engineering Technology
Office of Nuclear Reactor Research
U.S. Nuclear Regulatory Commission
Washington, DC 20555-0001
Under Interagency Agreement DOE 40-550-75
NRC FIN A-1010
Abstract
A series of experiments are described which evaluate the effects of test furnace pressure differential and excess pyrolyzates on the fire resistance of cable penetrations installed in fire resistive walls. It is shown that the measured fire resistance of penetrations can be strongly influenced by the pressure difference between the test furnace and the unexposed face of the penetration, and, to a lesser degree, by the presence or absence of excess pyrolyzates. Methods for the local introduction of excess pyrolyzates into a fire test furnace are discussed.