CR79023
November 19, 1979
MEMORANDUM FOR: B. H. Grier, Director, Region I
J. P. O'Reilly, Director, Region II
J. G. Keppler, Director, Region III
K. V. Seyfrit, Director, Region IV
R. H. Engelken, Director, Region V
FROM: Harold D. Thornburg, Director, Division of Reactor
Construction Inspection, IE
SUBJECT: IE CIRCULAR NO. 79-23 - MOTOR STARTERS AND CONTRACTORS
FAILED TO OPERATE
The subject Circular is transmitted for issuance on November 26, 1979. The
Circular should be issued to all power reactor operating facilities and
holders of reactor construction permits.
The text of the circular and draft letter to the licensees and permit
holders are enclosed for this purpose.
Harold D. Thornburg, Director
Division of Reactor Construction
Inspection
Office of Inspection and Enforcement
Enclosures
1. Draft transmittal letter
2. IE Information Notice No. 79-23
CONTACT: W. Laudan, IE
49-27551
.
(Draft letter to all power reactor operating facilities and holders of
reactor construction permits.)
IE Circular No. 79-23
Gentlemen:
The enclosed Circular 79-23 is forwarded to you for your information. No
written response to this circular is required. If you have any questions
related to the subject, please contact this office.
Sincerely,
Signature
(Regional Director)
Enclosure:
1. IE Circular No. 79-23
.
UNITED STATES SSINS No.: 6830
NUCLEAR REGULATORY COMMISSION Accession No:
OFFICE OF INSPECTION AND ENFORCEMENT 7910250496
WASHINGTON, D.C. 20555
November 26, 1979
IE Circular No. 79-23
MOTOR STARTERS AND CONTRACTORS FAILED TO OPERATE
Gould, Inc., Electrical Products Group, reported to the NRC on September 11,
1979 potential defects in certain NEMA size 3, Starters and Contractors. A
possible binding or seizure of the carrier assembly, within the support
plate of the stationary contact assembly, is caused by an undersized
dimension of the support legs.
Starters and contractors with date code 7822 to 7935, model and serial
numbers A1O, A11, A12, A13, A14, A20, A21, A22, and P1O are involved. Faulty
units were manufactured and distributed between June 1, 1978 and August 30,
1979. The attached listing of nuclear plants, which have received some of
this motor control equipment, represents a preliminary check of shipment
records. This listing, however, may not be complete.
Gould, Inc., will recall uninstalled items for retrofit and has retrofit
kits available for field installation.
Based on the above, licensees are advised to verify all motor starter and
contractor shipments received from Gould, Inc., between June 1, 1978 and
August 30, 1979, and assure that applicable model and serial number
components are corrected by retrofit and subsequent electrical operation
tests.
No written response to this Circular is required.
If you desire additional information regarding this matter, contact the
Director of the appropriate NRC Regional Office.
Attachments:
1. List of Plants that may have
Received Defective Starters
or Contractors
2. List of Recently Issued IE
Circulars
.
Enclosure: 1
According to a preliminary check of Gould's shipment records, the
following nuclear facilities have been shipped motor control equipment
which could include one or more defective NEMA Size 3 starters or
contractors:
Purchase Date
Facility Owner/Contractor Order Shipped
Farley Nuclear Plant, Unit 1 Alabama Power FNP1-3676 7-21-78
Operation 8-77 Bechtel FNP2-131 7-20-78
FNP2-125B 4-24-79
Arkansas Nuclear Plt. One Arkansas Power & 6600-E2011-AC 12-18-78
Unit 2 Operation 12-77 Light Bechtel Rev. 1B
Sharon Harris Nuclear Plt. Carolina Power and NY-435120 7-31-79
Unit 1 Construction Light Ebasco 8-20-79 8-31-79
Zimmer Nuclear Station Unit 1 Cincinnati G & E Z-50001 12-14-78
Construction
Midland Consumers Power Co. 7220-E-7-AC Various
Construction Bechtel Shipment in
78 & 79
Fermi 2 Nuclear Station Detroit Edison 1E-90235 8-14-78
Construction Sargent & Lundy Change Order 6
Beaver Valley Unit 2 Duquesne Light Co. 2BV-310 Various
Construction Stone & Webster Shipment in
78 & 79
Clinton Nuclear Station Units Illnois Power Co. Contract K-2976 8-24-78
1&2 Construction Baldwin Assoc.
Wolf Creek Unit 1 Kansas Gas & 10466-E-018-1 Various
Construction Electric Bechtel Shipment in
(SNUPPS) 78 & 79
San Onofre Nuclear Gen, Limitorque 3A4777 12-26-78
Sta 2/3 Construction
Kuosheng Nuclear Pwr. Sta. Taiwan Power Co. 9713-E-0003A 1-8-79
Units 1&2 Construction Bechtel
Bellefonte Nuclear Plant T V A 76K5-86242 Various
Construction shipment in
78 & 79
Watts Bar Units 1&2 T V A 74C5-84646 Various
Construction shipments
in 78 & 79
Page 1 of 2
.
Continued Page 2 of 2
Facility Owner/Construction Order Shipped
Callaway Unit 1 Union Electric 10466-E-018-2 Various
Construction Bechtel (SNUPPS) shipments
in 78 & 79
WPPSS Nuclear Project Unit 2 WPPSS Contract No. Various
Construction Burns & Roe 49 C/D 7 shipments
in 78 & 79