UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF INSPECTION AND ENFORCEMENT
WASHINGTON, D.C. 20555
March 8, 1979
IE Bulletin No. 79-02
PIPE SUPPORT BASE PLATE DESIGNS USING CONCRETE EXPANSION ANCHOR BOLTS
Description of Circumstances:
While performing inservice inspections during a March-April 1978 refueling
outage at Millstone Unit 1, structural failures of piping supports for
safety equipment were observed by the licensee. Subsequent licensee
inspections of undamaged supports showed a large percentage of the concrete
anchor bolts were not tightened properly.
Deficiency reports, in accordance with 10 CFR 50.55(e), filed by Long Island
Lighting Company on Shoreham Unit 1, indicate that design of base plates
using rigid plate assumptions has resulted in underestimation of loads on
some anchor bolts. Initial investigation indicated that nearly fifty percent
of the base plates could not be assumed to behave as rigid plates. In
addition, licensee inspection of anchor bolt installations at Shoreham has
shown over fifty percent of the bolt installations to be deficient.
Vendor Inspection Audits by NRC at Architect Engineering firms have shown a
wide range of design practices and installation procedures which have been
employed for the use of concrete expansion anchors. The current trends in
the industry are toward more rigorous controls and verification of the
installation of the bolts.
The data available on dynamic testing of the concrete expansion anchors show
fatigue failures can occur at loads substantially below the bolt static
capacities due to material imperfections or notch type stress risers. The
data also show low cycle dynamic failures at loads below the bolt static
capacities due to joint slippage.
Action to be Taken by Licensees and Permit Holders:
For pipe support base plates that use concrete expansion anchor bolts in
Seismic Category I systems as defined by Regulatory Guide 1.29, "Seismic
Design Classification" Revision 1, dated August 1973 or as defined in the
applicable FSAR.
1. Verify that pipe support base plate flexibility was accounted for in
the calculation of anchor bolt loads. In lieu of supporting analysis
justifying the assumption of rigidity, the base plates
1 of 3
.
IE Bulletin No. 79-02 March 8, 1979
should be considered flexible if the unstiffened distance between the
member welded to the plate and the edge of the base plate is greater
than twice the thickness of the plate. If the base plate is determined
to be flexible, then recalculate the bolt loads using an appropriate
analysis which will account for the effects of shear - tension
interaction, minimum edge distance and proper bolt spacing. This is to
be done prior to testing of anchor bolts. These calculated bolt loads
are referred to hereafter as the bolt design loads.
2. Verify that the concrete expansion anchor bolts have the following
minimum factor of safety between the bolt design load and the bolt
ultimate capacity determined from static load tests (e.g. anchor bolt
manufacturer's) which simulate the actual conditions of installation
(i.e., type of concrete and its strength properties):
a. Four - For wedge and sleeve type anchor bolts,
b. Five - For shell type anchor bolts.
3. Describe, the design requirements if applicable for anchor bolts to
withstand cyclic loads (e.g. seismic loads and high cycle operating
loads).
4. Verify from, existing QC documentation that design requirements have
been met for each anchor bolt in the following areas:
(a) Cyclic loads have been considered (e.g. anchor bolt preload is
equal to or greater than bolt design load). In the case of the
shell type, assure that it is not in contact with the back of the
support plate prior to preload testing.
(b) Specified design size and type is correctly installed (e.g. proper
embedment depth).
If sufficient documentation does not exist, then initiate a testing
program that will assure that minimum design requirements have been met
with respect to sub-items (a) and (b) above. A sampling technique is
acceptable. One acceptable technique is to randomly select and test one
anchor bolt in each base plate (i.e. some supports may have more than
one base plate). The test should provide verification of sub-items (a)
and (b) above. If the test fails, all other bolts on that base plate
should be similarly tested. In any event, the test program should
assure that each Seismic Category 1 system will perform its intended
function.
2 of 3
.
IE Bulletin No. 79-02 March 8, 1979
5. All holders of operating licenses for power reactor facilities are
requested to complete items 1 through 4 within 120 days of date of
issuance of this Bulletin. A reactor shutdown is not required to be
initiated solely for purposes of this inspection above. Maintain
documentation of any sampling inspection of anchor bolts required by
item 4 on site and available for NRC inspection. Report in writing
within 120 days of date of Bulletin issuance, to the Director of the
appropriate NRC Regional Office, completion of your verification and
describe any discrepancies in meeting items 1 through 4 and, if
necessary, your plans and schedule for resolution. For planned action,
a final report is to be submitted upon completion of your action. A
copy of your report(s) should be sent to the United States Nuclear
Regulatory Commission, Office of Inspection and Enforcement, Division
of Reactor Operations Inspection, Washington, D.C. 20555. These
reporting requirements do not preclude nor substitute for the
applicable requirements to report - as set forth in the regulations and
license.
6. All holders of construction permits for power reactor facilities are
requested to complete items 1 though 4 for installed pipe 1 support
base plates with concrete anchor bolts within 120 days of date of
issuance of this Bulletin. For pipe support base plates which have not
yet been installed, document your actions to assure that items 1 though
4 will be satisfied. Maintain documentation of these actions on site
and available for NRC inspection. Report in writing within 120 days of
date of Bulletin issuance, to the Director of the appropriate NRC
Regional Office, completion of your review and describe any
discrepancies in meeting items 1 though 4 and, if necessary, your plans
and schedule for resolution. A copy of your report should be sent to
the United States Nuclear Regulatory Commission, Office of Inspection
and Enforcement, Division of Reactor Construction Inspection,
Washington, D.C. 20555.
Approved by GAO B180225 (ROO72); clearance expires 7/31/80. Approval was
given under a blanket clearance specifically for identified generic
problems.
Enclosure:
List of IE Bulletins
Issued in Last
Twelve Months
3 of 3
Page Last Reviewed/Updated Thursday, March 29, 2012

