U.S. Nuclear Regulatory Commission Operations Center Event Reports For 03/10/2011 - 03/11/2011 ** EVENT NUMBERS ** | Power Reactor | Event Number: 46666 | Facility: KEWAUNEE Region: 3 State: WI Unit: [1] [ ] [ ] RX Type: [1] W-2-LP NRC Notified By: SCOTT CIESLEWICZ HQ OPS Officer: MARK ABRAMOVITZ | Notification Date: 03/10/2011 Notification Time: 18:29 [ET] Event Date: 03/10/2011 Event Time: 15:49 [CST] Last Update Date: 03/10/2011 | Emergency Class: NON EMERGENCY 10 CFR Section: 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION 50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE | Person (Organization): BILLY DICKSON (R3DO) | Unit | SCRAM Code | RX CRIT | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode | 1 | N | N | 0 | Refueling Shutdown | 0 | Refueling Shutdown | Event Text INADVERTANT OPENING A SUBSTATION BREAKER CAUSING LOSS OF STATION POWER "At 1549 on 03/10/2011 with the plant shut down and the reactor defueled, power was lost to Safeguards 4160 Volt Bus 6. Diesel Generator B started and re-energized Bus 6. "At the time of the event, Bus 6 was energized from the Main Auxiliary Transformer (MAT) on backfeed. The event was caused by opening of substation breaker TA2066 as the result of an error by technicians working In the substation. "All equipment operated as expected for the voltage restoration to Safeguards Bus 6. Safeguards Bus 5 remained energized from offsite power through the Tertiary Auxiliary Transformer during the event. "Spent Fuel Pool Cooling Train A remained In operation during the event. Spent Fuel Cooling Train B was restarted following restoration of power to Bus 6. "The loss of the MAT also resulted in the loss of non-safeguards 4160 V Buses 1-4. In response to the loss of power to Bus 4, the Technical Support Center (TSC) / Station Blackout (SBO) Diesel started and failed to load onto 480 Volt Bus 46. This resulted in a loss of power to the Technical Support Center. The loss of power to the TSC is being reported as a loss of Emergency Assessment Capability. At 1632, the TSC/SBO Diesel Generator tripped due to the failure of the output breaker to close and provide power to its support equipment. The cause of the failure of the TSC/SBO output breaker to close is unknown at this time." The licensee is investigating the cause of the breaker being opened and failure of the TSC/SBO diesel to load. One Spent Fuel Pool cooling train was in service throughout the event and no pool heatup occurred. The licensee notified the NRC Resident Inspector. | Power Reactor | Event Number: 46667 | Facility: NINE MILE POINT Region: 1 State: NY Unit: [1] [2] [ ] RX Type: [1] GE-2,[2] GE-5 NRC Notified By: DAN COLEMAN HQ OPS Officer: JOE O'HARA | Notification Date: 03/11/2011 Notification Time: 02:32 [ET] Event Date: 03/10/2011 Event Time: 20:15 [EST] Last Update Date: 03/11/2011 | Emergency Class: NON EMERGENCY 10 CFR Section: 50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE | Person (Organization): SAM HANSELL (R1DO) | Unit | SCRAM Code | RX CRIT | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode | 1 | N | Y | 91 | Power Operation | 91 | Power Operation | 2 | N | Y | 100 | Power Operation | 100 | Power Operation | Event Text LOSS OF PRIMARY AND BACKUP METEROLOGICAL MONITORING EQUIPMENT ON BOTH TOWERS "Loss of power to radiological monitoring equipment (primary and backup). This constitutes a major loss of emergency assessment capability per Nine Mile Point procedures. The cause of the loss of monitoring equipment is a downed 13.2 kV power line. Monitoring capability was restored at 0100." The loss of power was caused by high winds, and the grid operator was able to restore power at 0100 EST. The NRC Resident Inspector has been notified. | Power Reactor | Event Number: 46668 | Facility: DIABLO CANYON Region: 4 State: CA Unit: [1] [2] [ ] RX Type: [1] W-4-LP,[2] W-4-LP NRC Notified By: K.R.THOMPSON HQ OPS Officer: JOE O'HARA | Notification Date: 03/11/2011 Notification Time: 04:40 [ET] Event Date: 03/11/2011 Event Time: 01:23 [PST] Last Update Date: 03/11/2011 | Emergency Class: UNUSUAL EVENT 10 CFR Section: 50.72(a) (1) (i) - EMERGENCY DECLARED | Person (Organization): THOMAS FARNHOLTZ (R4DO) JANE MARSHALL (IRD) ELMO COLLINS (RA) JACK GROBE (NRR) | Unit | SCRAM Code | RX CRIT | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode | 1 | N | Y | 100 | Power Operation | 100 | Power Operation | 2 | N | Y | 100 | Power Operation | 100 | Power Operation | Event Text NOTICE OF UNUSUAL EVENT AS A RESULT OF A TSUNAMI WARNING IN THE AREA The licensee declared a notice of unusual event as a result of a tsunami warning issued for the coastal areas of California. The tsunami warning is a result of a 8.9 magnitude earthquake off the coast of Japan. The licensee is in EAL HU1.5, 'Tsunami Affecting the Protected Area'. The NRC remains in the normal response mode. The NRC Resident Inspector has been notified. | |